Changing Setpoint
Change the target temperature setpoint on the Vector 8700
The unit must be powered up (START/RUN-OFF switch in the START/RUN position) or in PC mode, and the default screen must be displayed. Press the Back soft key if needed to return to the default screen.

Press the UP (▲) or DOWN (▼) arrow key to bring the displayed setpoint to the desired value. The setpoint changes 1° per press (or 0.1° if configured). Press and hold for continuous scrolling.
Press the EQUALS (=) key to save the new setpoint. The MessageCenter will display "SETPOINT CHANGED" for 10 seconds.
If you do NOT press the EQUALS (=) key, the setpoint screen will flash, the MessageCenter will display "SETPOINT NOT CHANGED", and the system will revert to the original setpoint. You MUST press EQUALS to save your change.
The default setpoint range is -22°F to +95°F (-30°C to +35°C). The control system may be configured with a different minimum and/or maximum. "MAX SETPOINT HAS BEEN REACHED" or "MIN SETPOINT HAS BEEN REACHED" will display in the MessageCenter when a limit is reached.
The control system always retains the last entered setpoint in memory.
The setpoint cannot be changed while viewing the Alarm List, Data List, or Functional Parameters, while the unit is in Pretrip, or while the unit is in Sleep mode.