Manual Defrost

How to manually start a defrost cycle on the Vector 8700

You can manually trigger a defrost cycle at any time as long as certain conditions are met. The system can also initiate defrost automatically via the defrost timer or defrost air switch.

Step 1: Press Manual Defrost Key

With the system powered up (START/RUN-OFF switch in the START/RUN position), press the MANUAL DEFROST key.

PC Mode Demo Only

This procedure may be demonstrated in PC mode, but the unit will not actually enter defrost.

Step 2: Confirm Defrost Started

If conditions for defrost are met, the status bar and Box Temperature display will change to "DEFROST". The MessageCenter will display "DEFROST CYCLE STARTED" for 10 seconds.

If conditions are not met, the MessageCenter will display "CANNOT START DEFROST CYCLE" for 5 seconds. This occurs when: • Box temperature is too warm — defrost termination sensor (1DTT) must be below 40°F (4.4°C) or supply air sensor (1SAT) must be below 45°F (7.2°C) • Engine has not run at least 15 seconds after starting • Unit is in PC mode • Unit is in Pretrip • There is an active shutdown alarm

Automatic Defrost

Defrost may also be initiated automatically at preset intervals by the system defrost timer or by the defrost air switch.

The defrost cycle terminates when the defrost termination temperature (1DTT) rises above 55°F (12.8°C). If the cycle does not end after a maximum of 45 minutes, it is terminated automatically and alarm 00054 (Defrost Not Complete) will activate.

After Alarm 00054

If alarm 00054 activates, the system will wait 1.5 hours of unit running time before attempting another automatic defrost cycle. Pressing the MANUAL DEFROST key will override this wait and start a defrost cycle immediately, as long as all conditions are met.