00021@vector-8700critical

Technician Reset Required

engine

Description

00011, 00012, or 00129 has shut the unit down three times within the past 2 hours with the shutdown configurations set to YES; engine operation shuts down the engine and unit and alarms, and electric operation does not activate.

Activation Conditions

The High Engine Temp Shutdown Configuration and/or Engine Oil Pressure Shutdown Configuration is/are set to YES, and 00011 Check Engine Oil Pressure, 00012 High Coolant Temperature, or 00129 Check Engine Coolant Sensor has become active and shut the unit down three times within the past 2 hours.

Unit Behavior

Engine Operation: Engine and unit shutdown and alarm. Electric Operation: This alarm will not activate in Electric Operation

Reset Conditions

Clear the alarm from inactive alarm list. This alarm and the alarm(s) that caused it can not be reset by turning switch OFF and then ON again.

Corrective Actions

1. Determine Which Alarm Activated This Alarm - Check active alarm list for Alarm 00011 Check Engine Oil Pressure, 00012 High Coolant Temperature, or 00129 Check Engine Coolant Sensor. One of these alarms will be present. Follow the troubleshooting steps for the alarm(s) found, and correct the alarm condition. All alarm conditions must be corrected. 2. Reset Alarm - Clear all inactive alarms. Refer to Section 5.2.2. All alarms must be cleared to start unit.