07008@vector-8600mtlow

Check Redundant Return Air Sensor

electrical

Description

The redundant return air sensor is out of range; the unit gives an alarm only.

Activation Conditions

The redundant return air sensor is not within the range of - 53 to +158°F (-47 to +70°C)

Unit Behavior

Alarm only.

Reset Conditions

Auto reset when Redundant return air Sensor is in range or, alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

Check Temperature Sensor – Inspect sensor and connections. Verify there is no damage to the sensor and no damage, moisture or corrosion in connectors.