07000@vector-8500medium

Economizer Temperature Sensor

refrigeration

Description

The economizer temperature sensor is out of range; engine and electric operation alarm only and the economizer is forced to STANDARD mode.

Activation Conditions

Economizer temperature sensor is out of range

Unit Behavior

Engine and Electric Operation: Alarm only. Economizer forced to STANDARD mode when alarm is active.

Reset Conditions

Auto reset or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

1. Check Sensor a. Inspect sensor and connector. Verify there is no damage to sensor, and no damage, moisture, or corrosion in connector. b. Check sensor resistance (Refer to Note 3 in Notes Section) 10,000 Ohms @ 77°F (25°C.) See Table 8–5 for complete table of temperatures and resistance values. 2. Check Sensor Wiring a. Inspect connector pins and terminals at sensor and connector 1-3MSM-6 and 17. (See wiring schematic Section 10.) Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors. b. Place the system in PC mode. Refer to Note 2 in Notes Section Disconnect sensor from harness. Check for 3.0 ± 0.1 VDC volts at harness plug between pins. This verifies microprocessor output and wiring connections to the sensor.