Technician Reset Required
engine
Description
Repeated shutdown alarms or other listed alarms have occurred enough times to require a technician reset; engine operation shuts down the engine and unit with an alarm, and electric operation will not activate this alarm.
Activation Conditions
The High Engine Temp Shutdown Configuration and/or Engine Oil Pressure Shutdown Configuration is/are set to YES, and either Alarm 00011 - Low Engine Oil Pressure, or Alarm 00012 - High Coolant Temperature has become active and shut the unit down three times within the past two hours. Alarm 00128 “Low/Unbalanced A/C Amps” occurs twice within the last two hours of engine running time, or consecutive alarms between 00041 “Engine Stall” and 00100 “Overload/Ground Fault” occur within the last two hours of engine running time. Alarm 02006 “Starter Output” occurs twice within one hour of engine running time.
Unit Behavior
Engine Operation: Engine and unit shutdown and alarm. Electric Operation: This alarm will not activate in Electric Operation
Reset Conditions
Clear the alarm from the inactive alarm list. This alarm and the alarm(s) that caused it can not be reset by turning switch OFF and then ON again.
Corrective Actions
1. Determine which alarm activated this alarm. a. Check active alarm list to determine what conditions activated the technician reset. b. Follow the troubleshooting steps for the alarm(s) found, and correct the alarm condition. All alarm conditions must be corrected. 2. Reset Alarm - Clear all inactive alarms. Refer to Section 5.2.2. All alarms must be cleared to start unit.