28002@vector-8500medium
No Comm from Door Switch
system
Description
The 3rd Party door switch has not communicated for 15 minutes; engine and electric operation alarm only.
Activation Conditions
The door switch configuration is configured as 3rd Party and no communications have been received for 15 minutes
Unit Behavior
Engine and Electric Operation: Alarm only.
Reset Conditions
Communications have been received from the door switch.
Corrective Actions
1. Check for proper APX Control System Configuration - Refer to Section 5.2.3 and Table 5โ1. 2. Make sure that all third party configurations are correct and software is current. Check Switch and Wiring - Inspect switch, connector pins and terminals. No physical damage to sensor. No damaged or corrosion in connections.