Check CDCON1 Coil
engine
Description
The condenser fan motor contactor circuit is shorted or open; the unit alarms only.
Activation Conditions
Condenser fan motor contactor (CDCON) circuit is shorted or open.
Unit Behavior
Engine and Electric Operation: Alarm only.
Reset Conditions
Auto Reset or alarm may be manually reset via keypad or by turning the unit off, then back on again.
Corrective Actions
1. Check CDCON a. Inspect contactor coil and connector. Verify there is no damage to coil, and no damage, moisture, or corrosion in connector. b. Check contactor coil resistance. Refer to Section 2.12 for contactor coil resistance values. Cannot be opened (infinite ohms), shorted (Zero Ohms) or shorted to ground. 2. Check CDCON Using Component Test Mode a. Use Component Test mode to energize CDCON. (Refer to Section 5.2.4) Verify Current Draw on Component Test mode Screen. Refer to Section 2.11 for correct electrical values. b. Check coil voltage between A1 and A2. Verify 12 VDC between A1 and A2. c. Check resistance at contacts. Verify contacts are closed at L1-T1, L2-T2, L3-T3. 3. Check CDCON Wiring - Inspect harness and control box connector pins and terminals. (See wiring schematic Section 10.3) Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.