22402@vector-8600mtmedium
MSM1 IN High Voltage
electrical
Description
Voltage to the sensors on the input board is greater than 5.5 VDC; the unit gives alarm only.
Activation Conditions
Voltage to the sensors on the input board is greater than 5.5 VDC
Unit Behavior
Engine and Electric Operation: Alarm only.
Reset Conditions
Auto reset when sensor voltage is correct, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
1 Check Wiring - If a transducer reading is not within a reasonable range of gauge reading, check wires to sensors for short. 2 Check CT Wiring - Check wires to sensor for short from another circuit. 3 Replace Main Microprocessor - Download data and replace MSM.