Actuator Abnormal ECU
electrical
Description
Actuator current is above 3.0A or below 80mA, and engine operation requires shutdown.
Activation Conditions
Actuator current >3.0A or < 80mA
Unit Behavior
Engine Operation: Required Shutdown. Electric Operation: Will not activate in electric operation.
Reset Conditions
If trigger on message not received for five seconds, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
1. Refer to 05012 Check ECU Power Circuit 2. Check Engine Control Unit (ECU) a. Check voltage from fuse F4 through PM-15 and SP-24 to ENCU-22. Verify correct fuse, see Figure 2.7. Must have minimum 11 VDC with the battery connected and SROS in the OFF position. b. Check voltage from PM-32 through SP-34. Must have minimum 11 VDC with SROS in the START/ RUN position. If no, energize the run relay output using component test mode (refer to Component Test Mode) and retest. c. Check for ground at ENCU-19 and PM-28. If ground not good, check connectors and wiring between terminals for damage, moisture or corrosion. d. Inspect engine speed sensor (ENSSN) and engine control unit (ECU) connector pins and terminals. Verify no physical damage to components, and no damage or corrosion in connectors.