26100@vector-8700high

No Comm from Micro to ECU

engine

Description

The main microprocessor cannot communicate with the ECU over the CAN bus, and engine operation shuts down and alarms.

Activation Conditions

Main microprocessor cannot communicate with the engine control unit over the CAN bus.

Unit Behavior

Engine Operation: Shutdown and alarm. Electric Operation: Will not activate in electric operation.

Reset Conditions

Auto reset when CAN communication is restored, alarm reset or alarm may be manually reset by turning the unit off, then back on again.

Corrective Actions

1. Check both active and inactive alarms for other “NO COMM” alarms. a. If more than one alarm, record all and proceed to step 2. b. If this is the only alarm, check for continuity: • CAN Hi: 1-2MSM-27 to SP-26 to ENCU-66. • CAN Lo: 1-2MSM-28 to SP-27 to ENCU-65 c. Replace ECU. 2. Check CAN bus a. Inspect connector pins and terminals on PM, 1-1MSM, 1-2MSM, ECU. No damaged or corrosion in connections. b. Check for CAN continuity: • CAN Hi: 1-2MSM-27 to SP-26 to ENCU-66. • CAN Lo: 1-2MSM-28 to SP-27 to ENCU-65. If good continuity is not present, check connectors and wiring between terminals for damage, moisture or corrosion. 3. Check system - Clear active and inactive alarms. Start unit and monitor for additional “NO COMM” alarms.