00040@vector-8600mtlow

Check Engine Preheat Circuit

engine

Description

Intake Air Heater amperage was below 25 Amps or above 70 Amps after 14 seconds of glow time, and the unit alarms only.

Activation Conditions

Engine Operation: Intake Air Heater amperage is less than 25 Amps, or greater than 70 Amps after 14 seconds of glow time (NOTE: This can only occur when the Engine Coolant Temperature is below 50°F (11°C) due to pre-heat time allowed. Refer to Table 3–1 for pre-heat times. Electric Operation: This alarm will not activate in Electric Operation.

Unit Behavior

Alarm Only

Reset Conditions

Auto Reset if amperage is between 4 to 55 amps for at least 14 seconds during the glow cycle, or alarm may be manually reset via keypad or by turning the unit off, then back on again.

Corrective Actions

1. Check For Alarm 05017 Check Engine Preheat Enable Circuit. Alarm conditions must be corrected and the alarm cleared to continue. 2. Check Engine Preheater Circuit a. Using Component Test mode, refer to Section 5.2.4, energize engine preheat circuit. Check displayed amp draw, must be greater than 70 amps. NOTICE DO NOT leave the air intake circuit energized for the full five minutes if full amperage is shown, as the intake air heater element life will be greatly shortened. b. Check for power at EPH +. Must have minimum 11 VDC. If not, check connectors and wiring between terminals for damage, moisture or corrosion. c. Replace PM with known good component. 3. Check Engine Preheater Circuit - Check resistance of EPH. Refer to Section 2.8 for specifications.