22402@x4-7300low
Check Remote Amber Light
electrical
Description
The MSM sensor supply voltage is above the 5.5V high limit, and the unit gives alarm only.
Activation Conditions
The Voltage Supply for the Sensors on the MSM is above the High voltage limit 5.5V
Unit Behavior
Alarm only.
Reset Conditions
Auto reset when sensor voltage is correct, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
1. Check Transducer Wiring Check wires to sensors for short. • For CSP: 1-3MSM-21, SP-44 and 1-3MSM-32 • For EVOP: 1-3MSM-11, SP-44 and 1-3MSM-22 • For CDP; 1-3MSM-20, SP-44, 1-3MSM-31 and 1-3MSM-9 2. Replace Micro Stepper Module: Download data and replace Micro Stepper Module. For complete Micro Stepper Module replacement instructions refer to Section 1.5.2.