20002@aspen-apuhigh
CCU IO CAN Fail
system
Description
No communication from the Climate Control Module, and the unit shuts down all modules except the Aspen Interface and alarm.
Activation Conditions
No communication from Climate Control Module
Unit Behavior
Shutdown all modules except the Aspen Interface and alarm. (The alarm will only display if the AI is communicating.) Climate Control Module status LED will illuminate steady green (not pulsing).
Reset Conditions
Auto reset when communication is restored, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
Replace Climate Control Module: Download data and replace CCM board.