00020@aspen-apumedium

Maximum Compressor Alarms

refrigeration

Description

High Discharge Pressure or Low Discharge Pressure happened 3 times within the last 2 hours with power on, and the alarm stays active through power cycle.

Activation Conditions

Alarms 00013 (High Discharge Pressure) or 00014 (Low Discharge Pressure) occur three times within the last two hours when power is ON. This alarm cannot be cleared from the active queue. If this alarm is activated, both this alarm and the alarm that caused it will remain in the active alarm queue after power cycle.

Unit Behavior

Compressor Only

Reset Conditions

Alarm reset from CabinTech

Corrective Actions

1. Determine which alarm activated this alarm a. Check active alarm list for Alarm 00013 HIGH DISCHARGE PRESSURE, 00014 LOW REFRIGERANT PRESSURE. One or more of these alarms will be present. b. Follow the troubleshooting steps for the alarm(s) found and correct the alarm condition. All alarm conditions must be corrected. 2. Reset Alarm - Clear all inactive alarms. All alarms must be cleared to start unit.