Low Level Fuel Warning
fuel
Description
Fuel is 15% or less for more than 30 seconds; engine operation gives alarm only, and electric operation does not activate.
Activation Conditions
The ECU circuit is energized (PM-32 to ENCU-44) and fuel level is 15% or less for more than 30 seconds.
Unit Behavior
Engine Operation: Alarm only. Electric Operation: Will not activate in electric operation.
Reset Conditions
Auto Reset when the ECU circuit is energized (3MM-9) and fuel level is above 17% for more than 30 seconds, or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again. NOTE Follow the Troubleshooting steps until a problem is found. Once a repair or correction is made, the active alarm should clear itself as described below. Operate the unit through the appropriate modes to see if any active alarm occurs.
Corrective Actions
1. Check for Low Fuel Level - Check fuel level in the fuel tank. Add fuel as needed to the fuel tank. 2. Check Fuel Level Sensor - Refer to procedure for alarm 00126 Check Fuel Sensor Circuit. Alarm condition must be corrected and the alarm cleared to continue.