00018critical

Low Refrigerant Pressure

refrigeration

Description

Suction pressure is too low, indicating possible refrigerant loss or restriction.

Activation Conditions

Suction pressure <-6.3 psig.

Unit Behavior

Shutdown.

Reset Conditions

Auto reset when suction pressure rises above 0.0 psig.

Corrective Actions

1. Visually inspect for refrigerant leaks (look for oil residue on fittings). 2. Run the automated Pretrip test. 3. Check the refrigerant charge level. 4. Initiate a manual defrost cycle โ€” ice buildup on the evaporator can cause low suction. 5. Check the evaporator coils for blockage. 6. Check system pressures.