26217@x4-7500high
EES Failure
system
Description
26201 EES SERVICE REQUIRED has been active for 250 hours, and the unit does a required shutdown.
Activation Conditions
Alarm “26201 - EES SERVICE REQUIRED” has been active for 250 hours.
Unit Behavior
Required Shutdown.
Reset Conditions
If trigger on message not received for five seconds, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
If the EES is no longer functional due to “26201 - EES SERVICE REQUIRED”, a 250 hour countdown timer will initiate. The time remaining before unit shutdown will be displayed. Once the timer reaches zero the unit will not run until the EES is repaired and the “26201 - EES SERVICE REQUIRED” alarm is no longer active.