00122@x4-7500medium

Check Return Air Sensor (RAT)

electrical

Description

Return air temperature sensor is out of range -53 to +158°F (-47 to +70°C); the unit alarms and switches to supply air control, or enters Cargo Protect mode if 00123 is active.

Activation Conditions

Return Air Temperature Sensor (RAT) is not within range of -53 to +158°F (-47 to +70° C).

Unit Behavior

If Alarm 00123 Check Air Supply Sensor is not active: Alarm and switch to supply air control. If Alarm 00123 Check Air Supply Sensor is active: Alarm and the System will enter Cargo Protect mode. Refer to Section 4.11.1.

Reset Conditions

Auto reset when sensor is in range or, alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

1. Check Sensor a. Inspect sensor and connectors. Verify there is no damage to sensor, and no damage, moisture, or corrosion in connectors. b. Check sensor resistance. (Refer to Note 3 in Section 7.2) 10,000 Ohms @ 77°F (25°C). Refer to Section 1.9.21 for chart of resistances for different sensors. 2. Check Sensor Wiring a. Inspect connector pins and terminals at sensor connector 2MM. (See wiring schematic Section 1.) Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors. b. Place system in PC mode. Refer to Note 2 in Section 7.2. Disconnect sensor from harness. Check for 3.0 ± 0.1 VDC at harness plug between pins. Voltage should be 3.0 ± 0.1 VDC volts at harness plug between pins. This verifies microprocessor output and wiring connections to the sensor.