P00160@vector-8600mtlow
Check Discharge Temperature Sensor
refrigeration
Description
The compressor discharge temperature sensor is out of range, and pretrip fails with “PRETRIP FAIL AND COM- PLETED”.
Activation Conditions
Compressor Discharge Temperature Sensor (CDT) is not within the range of -40 to +392°F (-40 to +200°C.)
Unit Behavior
Engine and Electric Operation: Pretrip will fail and display “PRETRIP FAIL AND COM- PLETED”.
Reset Conditions
Auto reset if Pretrip is started again or alarm may be manually reset using the display mounted keys or by turning the unit off then back on again.
Corrective Actions
Check sensor operation - Refer to procedure for alarm 00125 Check Comp Discharge Sensor. Alarm condition must be corrected and the alarm cleared to continue.