00018@x4-7700high

Low Refrigerant Pressure

refrigeration

Description

Suction pressure is too low under the listed conditions, and the unit alarms only or shuts down and alarms if configured.

Activation Conditions

The compressor is operating with the suction pressure less than -3 psig (-0.20 bar) for more than the LP SHUTDOWN DELAY Configuration (up to five minutes) with RAT above -10°F (-23.3°C) or less than -8 psig (-0.53 bar) with RAT at any temperature.

Unit Behavior

Alarm only or (if configured for shutdown) shutdown and alarm.

Reset Conditions

Auto reset after 15 minutes if suction pressure is more than -2 psig (-0.13 bar) or alarm may be manually reset using the display mounted keys or by turning the unit OFF, then ON again.

Corrective Actions

1. Visually Inspect Unit: Look for damage to the liquid line causing a restriction or any signs of temperature drop at the filter drier. Verify that all tubing from the receiver to the evaporator section is in good condition. Verify that there is no temperature drop at the filter drier or anywhere on the liquid line. 2. Check Airflow Through Evaporator Coil/Section a. Inspect coil. Ninety percent or more of the coil surface must be undamaged. Coil must be clean. b. Check airflow (with unit running). Verify that there is even airflow through the entire coil and no “dead” spots. c. Check return air bulkhead, air chute. Verify that there is good air flow, return air not restricted and the air chute in good condition. d. Check that the fan clutch is fully engaged. e. Check upper and lower fan belt tension and condition. Verify that there is no glazing, cracking or slipping. Refer to Section 8.6. Replace if required. 3. Check Refrigerant Charge: Refer to Section 8.7.2. 4. Check System Pressures: Install manifold gauge set and check and compare compressor discharge, suction and evaporator outlet pressure to the Unit Data readings. Suction pressure must be above -3 psig (-0.2 bar). Refer to Section 8.9.10 for instruction on comparison. 5. Manually Defrost Unit: Defrost unit and terminate automatically. Typical defrost cycle time is 5-20 minutes. Visually verify that all ice is cleared from evaporator coil. 6. Perform Pretrip Check: Clear Active Alarm list, then run Pretrip and check for any new alarms. Any active alarms must be corrected and cleared before proceeding. 7. Check Unloader Operation: Check Front (UL1) and Rear (UL2) Unloaders. Refer to alarm 00085 Check UL1 Circuit and 00086 Check UL2 Circuit. 8. Check Compressor Suction Modulation Valve (CSMV): Refer to Section 8.9.6. 9. Check Expansion Valve (EVXV): Refer to Section 8.9.7.