26222@x4-7500high
EES Back Pressure Offset Exceeded
refrigeration
Description
Back pressure offset calibration is out of range; the unit is off, the transducer is not reading expected pressure, and shutdown is required.
Activation Conditions
The back pressure offset calibration is out of range. The unit is off and the back pressure transducer is not showing expected pressure readings. “26201 - EES SERVICE REQUIRED” will also be active in conjunction with this alarm.
Unit Behavior
Required Shutdown.
Reset Conditions
If trigger on message not received for five seconds, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
1. Check the back pressure transducer. 2. “26201 - EES SERVICE REQUIRED” will also be active in conjunction with this alarm. 3. Check for other alarms in queue and inspect the EES.