00255@vector-8600mthigh

Microprocessor Error

system

Description

The main microprocessor input and/or output board configuration is incorrect, and the unit shuts down and alarms.

Activation Conditions

If alarm 21100 “NO COMM FROM MICRO TO DISPLAY” is not active and main microprocessor input and/or output board configuration is incorrect.

Unit Behavior

Engine and Electric Operation: Shutdown and alarm.

Reset Conditions

Auto reset when board communications are valid, or alarm may be manually reset by turning the unit off, then back on again.

Corrective Actions

1. Check Software Revision - Check microprocessor software. The unit should have the software upgraded to the latest version, provided for Carrier Transicold dealers on the Carrier SolutionCenter (formerly TransCentral). 2. Reset Microprocessor a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, Wait 20 seconds and reinstall. Then place the START/RUN-OFF back in the START/RUN position. The microprocessor powers up OK and the latest setpoint appears in the display. b. Alarm 00255 remains active. Download data and replace the Microprocessor/Stepper module (MSM). Refer to Section 5.4.