00030@x4-7500high

Failed to Run Minimum Time

refrigeration

Description

Failed to run minimum time means the unit shut down on an alarm three times without running 15 minutes between shutdowns, and the unit alarms only or shuts down and alarms.

Activation Conditions

If Configured STANDARD: The unit has shutdown on an alarm three times without having run for at least 15 minutes between each shutdown (not including door switch shutdowns). If Configured RAIL: The unit has shutdown on an alarm and attempted to restart for the configured number of times without having run for at least 15 minutes between each shutdown (not including door switch shutdowns).

Unit Behavior

Alarm only or shutdown and alarm.

Reset Conditions

Alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again. If the Configuration is set to Rail mode, this alarm will reset after 4 hours and a rail alarm reset will be recorded in the data recorded.

Corrective Actions

Check For Shutdown Alarms: Alarm conditions must be corrected and alarm(s) cleared to continue.