Failed to Run Minimum Time
refrigeration
Description
Failed to run minimum time means the unit shut down on an alarm three times without running 15 minutes between shutdowns, and the unit alarms only or shuts down and alarms.
Activation Conditions
If Configured STANDARD: The unit has shutdown on an alarm three times without having run for at least 15 minutes between each shutdown (not including door switch shutdowns). If Configured RAIL: The unit has shutdown on an alarm and attempted to restart for the configured number of times without having run for at least 15 minutes between each shutdown (not including door switch shutdowns).
Unit Behavior
Alarm only or shutdown and alarm.
Reset Conditions
Alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again. If the Configuration is set to Rail mode, this alarm will reset after 4 hours and a rail alarm reset will be recorded in the data recorded.
Corrective Actions
Check For Shutdown Alarms: Alarm conditions must be corrected and alarm(s) cleared to continue.