26219@x4-7500high

Temp Sensor Drift

refrigeration

Description

One temperature sensor differs by more than +/-54°F (30°C) from the average of all three sensors, and the unit does a required shutdown.

Activation Conditions

One of the three temperature sensors differs Drift more than +/-54°F (30°C) from the average temperature of all the temperature sensors.

Unit Behavior

Required Shutdown.

Reset Conditions

If trigger on message not received for five seconds, alarm reset or alarm may be manually reset by turning the unit off, then back on again.

Corrective Actions

1. Check the temperature value of all temperature sensors using Unit Data. See unit's Operator's manual for information on viewing Unit Data. 2. Look for a temperature sensor that differs more than +/-54°F (30°C) from the average temperature and replace that sensor. 3. Temperature sensor drift is checked five hours after the START/RUN-OFF switch (SROS) has been switched off.