00059@x4-7700low

DataLogger (DataLink data recorder) Not Recording

system

Description

No data is being recorded by the DataLink data recorder; alarm only.

Activation Conditions

No data is being recorded by the DataLink data recorder.

Unit Behavior

Alarm only.

Reset Conditions

Alarm may be manually reset using the display mounted keys.

Corrective Actions

1. Clear Alarm a. Clear Active Alarm(s). b. Check for Active Alarm re-occurrence. If inactive, download all data and retain. If active, go to next step. 2. Micro Stepper Module (MSM) Defective a. Download previous data using a Data Transfer USB memory device or TRU-Tech. Data retrieval OK. b. Replace and setup MSM. Refer to Section 5.5. NOTE Specific Configurations may be found on the Carrier SolutionCenter (authorized Carrier Transicold Dealers only).