P00153@vector-8600mtlow
Check Return Air Sensor
electrical
Description
The return air temperature sensor is out of range, and pretrip fails with “PRETRIP FAIL AND COM- PLETED”.
Activation Conditions
Return Air Temperature Sensor (RAT) is not within the range of -53 to +158°F (-47 to +70°C).
Unit Behavior
Engine and Electric Operation: Pretrip will fail and display “PRETRIP FAIL AND COM- PLETED”.
Reset Conditions
Auto reset if Pretrip is started again, or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.
Corrective Actions
Check sensor operation - Refer to procedure for alarm 00122 Check Return Air Sensor. Alarm condition must be corrected and the alarm cleared to continue.