P00177@x4-7300low

Check EXV (EVXV) Superheat

refrigeration

Description

In Test #11, closing EVXV to 0% does not drop evaporator pressure by 20 psig (1.36 bar) or below 0 psig/bar, or EVXV does not open fully, and Pretrip fails.

Activation Conditions

With the unit running in Test #11, after the control system closes the EVXV to 0%, evaporator pressure fails to drop by 20 psig (1.36 bar) or fails to go below 0 psig / bar OR the EVXV appears not to be opening to the full capacity position.

Unit Behavior

Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.

Reset Conditions

Auto reset if Pretrip is started again or alarm may be manually reset using the display mounted keys or by turning the unit off then back on again.

Corrective Actions

1. Check Refrigerant Level: Refer to Section 1.7.2. 2. Check System Pressures: Install manifold gauge set to check and compare actual compressor discharge and suction pressures with those shown on the microprocessor display. Suction and Evaporator Outlet pressures must be above 3 psig (0.2 bar.) Refer to Section 1.9.12 for instruction on comparison. 3. Check EVXV a. Visually inspect EVXV for damage. Check to see if coil is seated on valve properly. b. Inspect EVXV coil and wire connections. Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors. c. Check EVXV operation. See Section 1.9.9. d. Check basic refrigeration system. Pressures normal. Compressor operation normal. e. Check the EVXV electrical system for good continuity in all circuits from microprocessor to EVXV. f. Inspect component and wire connections. No physical damage to harness. g. Inspect harness connector pins. (See wiring schematic Section 1.) Verify there is no damage, moisture, or corrosion in connectors. 4. Check EVOT: Check the sensor. Refer to procedure for alarm 00131 Check Evap Temp Sensor.