P00154@vector-8500low

Check Supply Air Sensor

electrical

Description

Supply air temperature sensor is out of range, and pretrip will fail and show “PRETRIP FAIL AND COMPLETED”.

Activation Conditions

Supply Air Temperature Sensor (SAT) is not within the range of -53 to +158°F (-47 to +70°C).

Unit Behavior

Engine and Electric Operation: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.

Reset Conditions

Auto reset if Pretrip is started again, or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

Check sensor operation - Refer to procedure for alarm 00123 Check Supply Air Sensor. Alarm condition must be corrected and the alarm cleared to continue.