24100@vector-8600mthigh
No Comm From Micro To Ccb1
system
Description
No communication from the CCB1 Module for 10 seconds when alarm 21100 is not active and the unit is not starting in diesel; the unit requires shutdown and, if active 2 minutes, shuts all modules except the display.
Activation Conditions
Alarm 21100 is not active, and Unit is not starting in diesel. No communication from the CCB1 Module for 10 seconds.
Unit Behavior
Engine and Electric Operation: Required Shutdown. If alarm remains active for 2 minutes issue a shutdown command to all modules except the display.
Reset Conditions
Communication received from the CCB1 Module in the past 10 seconds or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
Refer to the manual troubleshooting procedure.