26203@x4-7300high
EES Low Back Pressure
refrigeration
Description
Back pressure is below the acceptable range, and the unit does a required shutdown.
Activation Conditions
Back pressure is below the acceptable range.
Unit Behavior
Required Shutdown.
Reset Conditions
If trigger on message not received for five seconds, alarm reset or alarm may be manually reset by turning the unit off, then back on again.
Corrective Actions
1. Check back pressure hose for cracks, leakage or blockage. 2. Replace hose if damage is found.