07001@vector-8700medium

Economizer Press Sensor

electrical

Description

Economizer pressure sensor is out of range, and the unit gives alarm only and forces STANDARD mode.

Activation Conditions

Economizer Pressure (ECOP) sensor is out of range.

Unit Behavior

Engine and Electric: Alarm only. Economizer forced to STANDARD mode when alarm is active.

Reset Conditions

Economizer Pressure sensor is in range or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

1. Check System Pressures a. Check Unit Data. Refer to Section 3.15. Compare the pressure readings for the ECOP, the CSP and the CDP. The ECOP should read between the CSP and the CDP, if not it indicates the ECOP has failed. Refer to Section 8.8.11 for instruction on comparison. If discharge pressure is in normal range, proceed to next step. b. Place the Unit in Service mode. Refer to Section 5.2.5. After the unit has equalized, compare the pressure readings for the ECOP, the CSP and the CDP. The ECOP the CSP and the CDP should all read within 5 psi, if not it indicates the ECOP has failed. Refer to Section 8.8.11 for instruction on comparison. 2. Check Economizer Pressure Sensor - Inspect sensor and connectors (1-3MSM-9, 10, and 33). Verify there is no damage to sensor, and no damage, moisture, or corrosion in connectors.