22402@vector-8700medium

MSM-1 in High Sensor Voltage

electrical

Description

MSM sensor voltage is greater than 5.5 VDC, and the unit gives alarm only.

Activation Conditions

The voltage supply for the sensors on the MSM is greater than 5.5 VDC

Unit Behavior

Engine and Electric Operation: Alarm only.

Reset Conditions

Auto reset when sensor voltage is correct, alarm reset or alarm may be manually reset by turning the unit off, then back on again.

Corrective Actions

1. Check Wiring - If a transducer reading is not within a reasonable range of gauge reading, check wires to sensors for short. • For CSP: 1-3MSM-21, 1-3MSM-9, and 1-3MSM-32 • For EVOP: 1-3MSM-11, 1-3MSM-9, AND 1-3MSM-22 • For CDP: 1-3MSM-20, 1-3MSM-9, and 1-3MSM-31 • For ECOP: 1-3MSM-10, 1-3MSM-9, AND 1-3MSM-33 2. Check Power Supply Enable Circuit - Check wiring from DM-7 to 1-3MSM-35 (including SP-31). 3. Replace Main Stepper Module - Download data and replace Main Stepper module. For complete Main Stepper module replacement instructions refer to Section 5.5.2.