P00206@vector-8500low

Check Condenser Fan Circuit

refrigeration

Description

CDCON contactor coil circuit is outside the normal 0.05 to 2.0 Amps (12 VDC) draw; pretrip fails and shows “PRETRIP FAIL AND COMPLETED”.

Activation Conditions

Normal draw for the CDCON contactor coil is 0.05 to 2.0 Amps (12 VDC). The circuit tests outside this range.

Unit Behavior

Engine and Electric Operation: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.

Reset Conditions

Auto Reset if Pretrip is started again, or alarm may be manually reset via keypad or by turning the unit off, then back on again.

Corrective Actions

1. Check CDCON a. Inspect CDCON contactor coil and wire connections.Verify there is no damage to coil, and no damage, moisture, or corrosion in connections. b. Check contactor coil resistance. Refer to Section 2.11. 2. Check CDCON Amp Draw - Check CDCON contactor coil amp draw. Use Component Test mode (Section 5.2.4) to test. Refer to Section 2.11 for amp values. View current draw in Component Test mode screen. 3. Check CDCON Wiring - Inspect harness and control box connector pins and terminals PM-30 to CDCON-A1 and CDCON1-A2 to ground. (See wiring schematic Section 10.2) Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.