P00186@x4-7700low
Check Evap Outlet Temp
refrigeration
Description
Check Evap Outlet Temp means the EVOT is not within -53 to +158°F (-47 to +70°C), and Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
Activation Conditions
Evaporator Outlet Temperature Sensor (EVOT) is not within the range of -53 to +158°F (- 47 to +70°C.)
Unit Behavior
Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
Reset Conditions
Auto reset if Pretrip is started again, or alarm may be manually reset via keypad or by turning the unit off, then back on again.
Corrective Actions
Check Sensor: Refer to procedure for alarm 00131 Check Evap Temp Sensor.