00085@x4-7700low

Check UL1 Circuit

electrical

Description

A problem was detected in the front unloader UL1 coil circuit, shorted when UL1 was commanded on and open at other times; alarm only.

Activation Conditions

A problem has been detected in the front unloader (UL1) coil circuit. If this alarm is activated while the control system is calling for UL1 to be energized, the circuit is detected shorted. If this alarm occurs at any other time, the circuit is detected open.

Unit Behavior

Alarm only.

Reset Conditions

Auto reset when the circuit is normal, or Alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

1. Check for Additional Alarms: If this alarm is activated in conjunction with other alarms (00031 Failed to Start - Auto Mode, 00041 Engine Stalled, 05012 Check ENCU Power Circuit, 00078 Check SV1 Circuit, 00079 Check SV4 Circuit, 05013 Check Clutch Circuit or 00086 Check UL2 Circuit) check F2 and F11. Fuses must be good. Replace fuse(s) as required, clear alarms, restart and check for repeat alarm(s). 2. Check Coil a. Inspect coil and connector pins and terminals. Verify that there is no damage to coil. Verify that there are no damaged or corroded pins. b. Check resistance of coil. Refer to Section 2.11 for specifications. c. Use Component Test mode (Refer to Section 5.2.4) to test actual current draw of the circuit. Refer to Section 2.11 for specifications. Verify that the actual current is within specifications. 3. Check Power and Wiring a. Use Component Test mode (Refer to Section 5.2.4) to energize circuit. Check for power at UL1 terminal A and PM-7. Minimum 11 VDC. If not, check connectors and wiring between terminals. Verify that there is no damage, moisture or corrosion. b. Check for ground at UL1 terminal B (including SP-10) to GND RING1. Good ground. If not, check connectors and wiring between terminals. Verify that there is no damage, moisture or corrosion.