00056@x4-7300high

Check Evaporator Air Flow

refrigeration

Description

Evaporator airflow was out of range in heat or cool mode, and the unit shuts down and alarms.

Activation Conditions

In Heat mode, the suction pressure has been higher than 100 PSIG (6.8 bar) for more than 60 seconds OR In Cool mode, SAT is 5°F (2.8°C) or more warmer than RAT for 3.5 minutes. After the first occurrence of this alarm, the MessageCenter will display “NO TEMP CONTROL - SEE ALARM LIST”. NOTE For this alarm the unit must be running. This alarm will not occur in either the Defrost or Pretrip cycles.

Unit Behavior

Unit Shutdown and Alarm.

Reset Conditions

Auto reset in 15 minutes if Alarm 00030 Failed to Run Minimum Time is not also active or, alarm may be manually reset using the display mounted keys or by turning the unit off, then back on again.

Corrective Actions

1. Check Airflow Through Evaporator Coil/Section a. Inspect coil. Ninety percent or more of the coil surface must be undamaged. Coil must be clean. b. Check airflow (with unit running). Even airflow through the entire coil. No “dead” spots. c. Check return air bulkhead, air chute. Verify good air flow, and Return Air not restricted. Air chute in good condition. d. Check fan clutch. Must be fully engaged. Check upper and lower fan belt tension and condition. Verify no glazing, cracking, or slipping. Refer to Section 1.6. Replace if required. 2. Check System Pressures: Install manifold gauge set to check and compare actual compressor discharge and suction pressures with those shown in Unit Data. Refer to Section 1.9.12 for instruction on comparison. 3. Check Refrigerant Charge: Refer to Section 1.7.2. 4. Perform Pretrip Check: Run Pretrip and check for alarms. Any active alarms must be corrected and cleared before proceeding. 5. Check SV4: Refer to SV4 Checkout Procedure, Section 1.9.6. 6. Refer to Refrigeration Troubleshooting: Check low cooling capacity causes. Refer to Section 1.3.2 and Section 1.3.4.